Bow and stern thruster wiring: cable size and fuse, in AWG

A thruster pulls more current than anything else on your boat. The longer and thinner the cable, the more of that power turns to heat before it reaches the motor.

  • Worked to the US boat wiring standard
  • Figures from the makers' manuals
  • Long cable wastes power

The short answer

Some of the battery's power never reaches the motor. It turns to heat in the cable, and the farther away the battery, the more you lose.

How much power the cable loses, by how far away the battery is
Battery away Cable you buy Lost at 12 V Lost at 24 V
5 ft 10 ft 3 percent 1 percent
10 ft 20 ft 7 percent 2 percent
20 ft 40 ft 14 percent 4 percent
30 ft 60 ft 21 percent 5 percent

All four rows use the same 2/0 AWG cable. The motor draws 530 A at 12 volts and 280 A at 24 volts. The figures are our arithmetic, from copper's published resistance.

  1. Closer is better. With the battery 5 feet away, about 3 percent of the power is lost in the cable. Move it 20 feet away and you lose four times as much. Less power at the motor means less push, so put the battery near the thruster if you can.
  2. Twenty-four volts needs less copper. The same motor draws about half the current at 24 volts. On the same cable it loses about a quarter as much. The cost is a second battery, wired in series with the first.
  3. Measure both cables. Power goes out on the positive cable and comes back on the negative. A battery 20 feet away means 40 feet of cable to buy. Measure the route the cable will really follow.
  4. Use at least the maker's cable size. The installation manual names a cable size for your distance. Never go smaller. ABYC, the group that writes the US boat wiring standards, says the same.
  5. Put the maker's fuse at the battery. It goes within 7 inches of the battery, so it protects the whole cable. Use the size the manual names. It can look too small, and that is normal. Never fit a bigger one because the old one blew.
  6. Buy the cable by the foot. Some stores cut marine battery cable to the length you need. Defender sells tinned cable from $2.76 a foot to $13.25 a foot, the thickest. Prices read October 26, 2026.

The wiring calculator works this out for your own thruster and distance. Doing the install yourself? The DIY page says which jobs are yours and which to split with a yard.

Measure both legs of the run

Current goes to the thruster on the positive cable and comes back on the negative. A battery 20 feet away means 40 feet of cable. Size it as 20 feet and you end up one or two sizes too small.

Measure the route the cable will really follow: along the A long rib bonded inside the hull, running from bow to stern, that stiffens the bottom. Cutting through one weakens the boat, so a tunnel is kept clear of them., around tanks and over the A wall inside the boat, running across it from side to side.. It is longer than a tape down the middle of the boat.

Start from the maker's current draw

Every cable size starts from the current the thruster draws. Get it from the maker's manual, for your model at your voltage.

Do not work it out by dividing the motor's kW by the volts. Against the makers' own figures that comes out 17% to 41% short, as much as 217 A. A cable and fuse sized from it are both too small.

Show the table: the maker's real draw, against kW divided by volts (8 rows)
The maker's real draw, against kW divided by volts
Model Volts Rating Maker's stated draw kW divided by volts Amps missed Short by, as % of the real draw
SEP60/185S 24 V 2.4 kW 170 A 100 A 70 A 41%
SE80/185T 24 V 4.4 kW 280 A 183 A 97 A 35%
SE100/185T 24 V 6.3 kW 340 A 263 A 78 A 23%
SEP60/185S 12 V 3.1 kW 370 A 258 A 112 A 30%
SE210/250TC 24 V 10 kW 500 A 417 A 83 A 17%
SE80/185T 12 V 4.4 kW 530 A 367 A 163 A 31%
SE170/250TC 24 V 8 kW 550 A 333 A 217 A 39%
SE100/185T 12 V 6.3 kW 740 A 525 A 215 A 29%

The maker's stated current draw against what dividing the motor rating by the system voltage would have given you. From the Side-Power SE80/SE100 and SE170/SE210 installation manuals, read 4 September 2026.

What gauge you need

Cable is sold by AWG size. A smaller number is a thicker cable, and past 1 AWG the sizes run 1/0, 2/0, 3/0 and 4/0, the thickest. "2 x 1/0 AWG" means two 1/0 cables side by side, on both the positive and the negative.

The size has to pass two tests from The American Boat and Yacht Council, the body that writes the standards US boats are built and wired to. A surveyor or an insurer who asks whether wiring is to standard means ABYC’s., the US boat wiring standard. First, no more than 10 percent of the battery’s voltage may be lost in the cable. Second, ABYC’s table must rate the cable for the current. The standard takes the larger of the two sizes.

Show the table: cable sizes at ABYC's 10 percent loss limit, by distance (8 rows)
Cable sizes at ABYC's 10 percent loss limit, by distance
Model Draw 10 ft15 ft20 ft25 ft30 ft40 ft
SEP60/185S 24 V 170 A 2 AWG2 AWG2 AWG2 AWG2 AWG2 AWG
SE80/185T 24 V 280 A 1/0 AWG1/0 AWG1/0 AWG1/0 AWG1/0 AWG1/0 AWG
SE100/185T 24 V 340 A 3/0 AWG3/0 AWG3/0 AWG3/0 AWG3/0 AWG3/0 AWG
SEP60/185S 12 V 370 A 3/0 AWG3/0 AWG3/0 AWG3/0 AWG4/0 AWG2 x 2/0 AWG
SE210/250TC 24 V 500 A 2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG
SE80/185T 12 V 530 A 2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 2/0 AWG2 x 3/0 AWG2 x 4/0 AWG
SE170/250TC 24 V 550 A 2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG2 x 1/0 AWG
SE100/185T 12 V 740 A 2 x 3/0 AWG2 x 3/0 AWG2 x 3/0 AWG2 x 3/0 AWG2 x 4/0 AWGshorter run

The E-11 minimum, as E-11 section 11.15.1.2.7 directs. It is the larger of two sizes. The first is the smallest size ABYC's ampacity table rates for the draw, clear of the engine compartment. The second is the smallest size holding ABYC's 10 percent drop allowance. Distances are one way, battery to thruster. The arithmetic doubles them.

Sizes above 4/0 are given as paired conductors per leg, their ratings counted together. The makers' own tables do the same at length. A cell reading "shorter run" would take more than 2 conductors per leg by the drop, past what any maker's table asks for. The answer there is a battery nearer the thruster.

ABYC’s standard has a second, stricter limit for circuits where low loss matters: no more than 3 percent of the battery’s voltage lost in the cable. On a 12 volt boat that is about 0.36 volts. A thruster is not on ABYC’s list for it, the makers’ tables do not use it, and at 12 volts it takes far more copper.

Show the table: cable sizes at ABYC's stricter 3 percent limit (8 rows)
Cable sizes at ABYC's stricter 3 percent loss limit, by distance
Model Draw 10 ft15 ft20 ft25 ft30 ft40 ft
SEP60/185S 24 V 170 A 2 AWG1 AWG1/0 AWG2/0 AWG3/0 AWG4/0 AWG
SE80/185T 24 V 280 A 1/0 AWG2/0 AWG3/0 AWG4/0 AWG2 x 2/0 AWG2 x 3/0 AWG
SE100/185T 24 V 340 A 3/0 AWG3/0 AWG4/0 AWG2 x 2/0 AWG2 x 3/0 AWG2 x 4/0 AWG
SEP60/185S 12 V 370 A 2 x 2/0 AWG2 x 3/0 AWGshorter runshorter runshorter runshorter run
SE210/250TC 24 V 500 A 2 x 1/0 AWG2 x 2/0 AWG2 x 3/0 AWG2 x 4/0 AWGshorter runshorter run
SE80/185T 12 V 530 A 2 x 3/0 AWGshorter runshorter runshorter runshorter runshorter run
SE170/250TC 24 V 550 A 2 x 1/0 AWG2 x 2/0 AWG2 x 3/0 AWG2 x 4/0 AWGshorter runshorter run
SE100/185T 12 V 740 A shorter runshorter runshorter runshorter runshorter runshorter run

The same rule at ABYC's 3 percent allowance, for circuits where voltage drop must be kept to a minimum. It takes the larger of two sizes: the smallest the ampacity table rates for the draw, and the smallest holding 3 percent. "Shorter run" means more than 2 conductors per leg by the drop, where this site stops naming cable.

Stranded, tinned marine cable in a warm locker loses a little more than this arithmetic. Between two sizes, buy the larger. The wiring calculator runs it for your own thruster and distance.

How much current a cable can carry

Every cable size has a heat limit: the most current it can carry without overheating. ABYC, the group that writes the US boat wiring standards, publishes it for each size. The thickest common cable, 4/0, is rated 445 A, or 378 A where it runs through the hot engine room. A bigger thruster draws more than that, so it gets two cables side by side on each leg.

Pick the cable that passes two checks:

  1. It keeps the power lost under 10 percent for your distance, and it is rated for your thruster’s current.
  2. It is at least as heavy as the cable the maker’s manual names for your distance.

The maker’s cable is sometimes lighter than ABYC’s rating, because a thruster runs for only seconds at a time. ABYC makes no allowance for that, so go with the heavier of the two. The wiring calculator shows both for your boat. Checking your install is yours, or your surveyor’s.

Show the table: how many amps each cable size is rated to carry (10 sizes)
How many amps each cable size is rated to carry
Size Copper, to scale Clear of the engine room Through the engine room
8 AWG8.4 mm² 80 A 68 A
6 AWG13 mm² 120 A 102 A
4 AWG21 mm² 160 A 136 A
3 AWG27 mm² 180 A 153 A
2 AWG34 mm² 210 A 178.5 A
1 AWG42 mm² 245 A 208.3 A
1/0 AWG53 mm² 285 A 242.3 A
2/0 AWG67 mm² 330 A 280.5 A
3/0 AWG85 mm² 385 A 327.3 A
4/0 AWG107 mm² 445 A 378.3 A

ABYC E-11 Table 4A (July 2025 edition), allowable amperage of DC conductors when no more than two are bundled, sheathed or in conduit, 105 C insulation. The standard gives two figures for each size. The first is for a cable that stays clear of the engine compartment. The second, 15 percent lower, is for a cable that runs through it, where it is hot.

Every figure this site prints uses the first unless it says otherwise. A run that does pass through takes the second figure: a stern unit fed from the house bank, or a bow unit fed from a bank aft. The wiring calculator has a box for it.

The figures are read from the standard itself. The public reproductions of the older edition, the Paneltronics E-11 excerpt and the BoatHowTo wire size tables, give the same figures but leave out 3 AWG. A marine dealer's battery cable skips 3 AWG too, so no size on this site is 3 AWG.

The largest size that table carries is 4/0, at 445 amps clear of the engine compartment (378.3 through it). Four of the eight published draws above are higher than that:

  • SEP60/185S at 24 V, 170 A. Covered by a single 2, rated 210 amps clear of the engine compartment.
  • SE80/185T at 24 V, 280 A. Covered by a single 1/0, rated 285 amps clear of the engine compartment.
  • SE100/185T at 24 V, 340 A. Covered by a single 3/0, rated 385 amps clear of the engine compartment.
  • SEP60/185S at 12 V, 370 A. Covered by a single 3/0, rated 385 amps clear of the engine compartment.
  • SE210/250TC at 24 V, 500 A. No single conductor up to 4/0 is rated to carry it. Paired conductors per leg, which is what the maker specifies at length anyway.
  • SE80/185T at 12 V, 530 A. No single conductor up to 4/0 is rated to carry it. Paired conductors per leg, which is what the maker specifies at length anyway.
  • SE170/250TC at 24 V, 550 A. No single conductor up to 4/0 is rated to carry it. Paired conductors per leg, which is what the maker specifies at length anyway.
  • SE100/185T at 12 V, 740 A. No single conductor up to 4/0 is rated to carry it. Paired conductors per leg, which is what the maker specifies at length anyway.

The makers' own tables name single conductors well below these figures. The largest gap in Sleipner's published set is the SE100/185T at 12 volts. Its stated draw is 740 A, on the 3/0 AWG their table names for its 7 meter band.

That is 192% of what ABYC allows that size to carry clear of the engine compartment.

Two cables per leg: what ABYC asks

When you run two cables side by side on each leg, ABYC sets three rules:

  1. Both cables the same type, the same length and the same size.
  2. Run together in the same bundle or conduit.
  3. Both ends on the same terminal of the fuse.

Bundle the two positive cables together and the two negative cables together. Put all four in one bundle and each one is rated lower: a 4/0 drops from 445 A to 311.5 A.

The fuse. One fuse can protect both cables at their two ratings added together. Each cable must then be 2 AWG or larger, and the pair is labeled to say the fuse needs both cables connected. If each cable can carry the whole current on its own, the fuse only has to protect one cable.

Why the fuse is rated below the draw

The maker’s fuse often looks too small for the draw. That is normal. A slow A flat, bolt-down fuse made for heavy loads like a thruster or a windlass. It is built to carry a big overload for a while and open only on a short circuit. blows at 140 to 266 percent of its rating, says Blue Sea Systems, which makes them. It carries a big load for minutes and opens on a short.

ABYC treats a thruster as a motor. Nothing may catch fire if it stays switched on for seven hours under any overload, a jammed propeller included. That is why a maker’s fuse can sit above the rating of a light cable on a short run. A breaker on a thruster is the motor kind, marked OL1 or Full Load.

Lewmar prints a fuse for every model, and every one is below the draw. VETUS does the same on its brushed units. On most of its BOW PRO units the main fuse sits above the draw. Both are in The detail, under VETUS and Lewmar.

Fit the fuse the maker names for your model and voltage. The 12 volt and 24 volt versions of one thruster take different fuses.

Never fit a bigger fuse because the old one blew. It was doing its job, and the next thing in line is the cable.

Show Sleipner's fuses, model by model (5 rows)
Sleipner's fuses against the draw of the models they fit
Fuse Rating Sleipner says it fits Model here Stated draw Draw as % of fuse The guide's fuse
ANL500 500 A SE100/130 12V + SE210/240 24V SE210/250TC 24 V 500 A 100% ANL 400the draw is 125% of it
ANL250 250 A SE40/80 24V SE80/185T 24 V 280 A 112% ANL 250
ANL400 400 A SE80 12V + SE150/170 24V SE80/185T 12 V 530 A 133% ANL 400
ANL400 400 A SE80 12V + SE150/170 24V SE170/250TC 24 V 550 A 138% ANL 400
ANL500 500 A SE100/130 12V + SE210/240 24V SE100/185T 12 V 740 A 148% ANL 500

Sleipner ANL slow blow fuses and the models their own catalog names, quoted verbatim, against the stated draw of the models in our database, read 4 September 2026. The last column is the ANL the model's current installation guide prints on its Electrical Reference Guide page, read 25 September 2026 (the SE210, SE80 to SE150 and SE170 guides). The draw column is worked on the webshop's fuse.

The guides and the webshop agree on every row but one. The webshop lists the SE210/250TC at 24 V under the ANL500, and its guide prints ANL 400. Where the two differ, match the figure in your own unit's guide.

Of the five pairings in the table, one draws more than 140 percent of its fuse's rating. The SE100/185T at 12 volts draws 148% of its 500 amp fuse's rating. That is inside the range where an ANL may eventually open. It is why the manual insists the fuse hold the stated draw for five minutes, and why the thruster has a duty cycle in the first place.

Where the fuse goes: within 7 inches of the battery

The fuse goes at the battery end, within 7 inches of where the cable connects, measured along the cable. ABYC allows more only where the cable runs inside a protective sheath: up to 72 inches from a battery, or 40 from a A metal bar with several studs that joins many heavy cables at one point, so each does not have to reach the battery itself. (E-11 section 11.10.1.1.1.1).

The fuse protects the cable. If the cable chafes through anywhere, the whole battery bank feeds the short. A fuse at the battery protects all of the cable; one at the thruster protects almost none of it.

Use Squeezing a metal end onto a cable with a tool made for the size, so the copper and the end become one solid piece. It is how heavy marine cable is terminated, never soldered., sealed The metal end crimped onto a heavy cable so it can be bolted to a terminal., support the cable so its weight does not hang on the stud, and torque each one to the terminal maker’s figure. A loose connection carrying 740 A is a heater. If your thruster works but works badly, the not-working page covers it.

This cable carries hundreds of amps. Before you work on it, read the safety rules on the battery page.

What 24 volts does to the copper

The same motor draws about half the current at 24 volts. Sleipner’s SE100/185T draws 740 A at 12 volts and 340 A at 24 volts. With the battery 20 feet away it needs 2 x 3/0 AWG per leg at 12 volts and 3/0 AWG at 24 volts.

The cost is a second battery. Where the bank goes, how big and what type is on the battery page.

The detail

What each maker’s cable table says, worked through the same arithmetic, and what none of them publishes.

What Sleipner's cable table says

Sleipner is unusual in publishing a cable table at all. It is more unusual in printing an American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still. equivalent beside every metric size.

Its current guides print two sizes for each length of run: a minimum and a recommended one. The table below uses the recommended size, the same one each product page shows. In all 15 bands read here, the AWG size is the nearest match for the metric size beside it.

Show Sleipner's cable table (15 bands)
Sleipner recommended cable, total positive plus negative run, as published, with the resulting voltage drop computed at the top of each band. Read from Sleipner’s 2025 installation guides for the SE80 and SE100, SEP60, SE170 and SE210, 10 October 2026.
Model Volts Draw Run to Their mm² Their AWG Nearest AWG Drop at band top
SE80/185T 12 V 530 A 23.0 ft 70 2/0 2/0 7.6%
SE80/185T 12 V 530 A 45.9 ft 2 × 70 2 × 2/0 2 × 2/0 7.6%
SE80/185T 24 V 280 A 23.0 ft 35 2 2 4.0%
SE80/185T 24 V 280 A 45.9 ft 50 1/0 1/0 5.6%
SE100/185T 12 V 740 A 23.0 ft 95 3/0 3/0 7.8%
SE100/185T 24 V 340 A 23.0 ft 50 1/0 1/0 3.4%
SEP60/185S 12 V 370 A 23.0 ft 50 1/0 1/0 7.4%
SEP60/185S 12 V 370 A 45.9 ft 95 3/0 3/0 7.8%
SEP60/185S 24 V 170 A 23.0 ft 25 3 3 3.4%
SEP60/185S 24 V 170 A 45.9 ft 35 2 2 4.9%
SE100/185T 24 V 340 A 45.9 ft 70 2/0 2/0 4.9%
SE170/250TC 24 V 550 A 23.0 ft 70 2/0 2/0 4.0%
SE170/250TC 24 V 550 A 45.9 ft 95 3/0 3/0 5.8%
SE210/250TC 24 V 500 A 23.0 ft 70 2/0 2/0 3.6%
SE210/250TC 24 V 500 A 45.9 ft 95 3/0 3/0 5.3%

The drop column is the useful part. It is computed at the top of each band, where the run is longest and the drop is worst. There, Sleipner's recommended cable lands between 3.4% and 7.8%.

Of the 15 bands, none meets ABYC's tighter 3 percent figure, and none exceeds the 10 percent one at the very top of the band.

A run shorter than a band's limit does better, which is why the makers publish bands.

Sleipner also publishes a minimum battery for each model, in Cold cranking amps: how much current a battery can deliver in a short, hard burst, which is the rating starter batteries carry. A thruster draws like a starter, so the makers size its battery this way rather than by capacity.. Where the battery should live, what capacity it needs and why The drop in a battery’s voltage while a heavy load is drawing from it. The battery recovers when the load stops, but the motor only ever sees the sagged figure. costs you thrust have their own page: bow thruster batteries.

What Sideshift publishes: a start current, a cable size and a distance

Sideshift's A thruster that bolts to the outside of the hull, up near the bow or on the back of the boat. Its propeller hangs in the water below it. Nothing is cut through the hull, so there is no tunnel. carry their own motor controller. The maker publishes three things about the cable to it:

  • a start current per series
  • one American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still. size per series
  • how far away the battery may sit

The installation manual says the total cable run from the battery to the motor controller must not exceed 10 ft. The table computes the drop over that run.

Show Sideshift's figures by series (4 rows)
Sideshift's published electrical figures by series, read 23 September 2026. The start current, the cable size and the 10 ft run are from the Rev 3.1 installation manual. The drop is computed at the start current, on the maker's cable, over the manual's total run.
Series Volts Start current Their AWG Drop, manual's 10 ft
230 12 V 300 A 1/0 2.5%
240 24 V 200 A 2/0 0.6%
340 12 V 550 A 2/0 3.6%
350 24 V 400 A 2/0 1.3%

Inside the manual's 10 ft, the maker's own cable holds the drop to 0.6% to 3.6%, even at the start current.

That is inside ABYC's 10 percent allowance on every series. It is under the tighter 3 percent on three of the four.

The start current is a peak that lasts a moment, so the steady figure is lower. The maker does not publish the steady figure.

Keep the batteries within the manual's 10 ft and the maker's size computes inside the allowance.

The start currents run from 200 A to 550 A across the four series. The battery Sideshift asks for, and why it wants a starting battery rather than a deep-cycle one, is on the battery page. The Sideshift review reads the rest of the manual.

What VETUS publishes: a table per manual, built to half the drop its text allows

Every VETUS installation manual ends with the same table, headed "Battery capacity, battery cables". It gives:

  • the smallest and largest battery the unit may have
  • the total run of positive plus negative cable, in bands
  • the cable size for each band in mm², with an American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still. size beside it
  • the main fuse, with its part number

The text above the table says the drop "must not be more than 10% of the voltage supplied".

The table does not use that figure. Of the 42 rows, 27 come out between 4.3% and 5.1%. Those are every brushed unit but the BOW28548D, every 12 and 48 V BOW PRO but the BOWA0304, and the smallest Boosted unit. The drop is computed at the stated current, at the top of every band, on the metric size printed.

The other 13 Boosted units are built tighter, 0.3% to 3.3% of their 24 or 48 V bank. Two rows follow neither pattern, and the notes below say why.

A run inside a band does better than its top, so VETUS's minimum cable carries more margin than its text asks for. Of Sleipner's 15 bands, 8 compute to more than the five percent rows' highest.

The fuse VETUS names

VETUS prints a number. Every installation manual's table names a slow blow main fuse with its part number. On the brushed units it sits at 60% to 73% of the stated draw. For example, the BOW7512D draws 550 A and takes a 355 A fuse, ZE355.

Every BOW PRO but one runs the other way. There the main fuse is above the nominal draw, 104% to 222% of it. On the 110 to 250 mm units a smaller thruster fuse sits in the controller under it. The BOWA0651, which draws 237 A at 12 V, takes 300 A and 250 A.

The one exception is the BOWB420. It has a 500 A fuse on a 520 A nominal draw, 96% of it, and no thruster fuse. The full set is in the table below.

Show the VETUS table, one row per model and voltage (42 rows)
VETUS, one row per model and voltage, read 15 September 2026. The figures come from the "Battery capacity, battery cables" table and the technical data page of 21 installation manuals on vetus.com. The draw is the manual's stated current. On the BOW PRO it is the figure printed at the low voltage, the one the bands compute to. The first band is the shortest run and the smallest cable. The single-conductor limit is the longest run before the table asks for two conductors per leg. The drop is computed at the top of each band on the metric size, and the cell gives the range across the row's bands. Cable bigger than 4/0 is sold by MCM, thousands of circular mils. The next size up is 300 MCM.
Model Volts Draw Main fuse Fuse as % of draw Battery, minimum First band One conductor to Drop at band tops
BOW2512E 12 V 200 A 125 A ZE125 63% CCA 333 25 mm² (AWG 4) to 4.2 m, 13.8 ft 84.3 ft 150 mm² 4.7% to 4.9%
BOW3512E 12 V 220 A 160 A ZE160 73% CCA 367 25 mm² (AWG 4) to 3.8 m, 12.5 ft 76.8 ft 150 mm² 4.8% to 5.0%
BOW4512D 12 V 375 A 250 A ZE250 67% CCA 625 25 mm² (AWG 4) to 2.3 m, 7.5 ft 44.9 ft 150 mm² 4.8% to 5.0%
BOW5512D 12 V 375 A 250 A ZE250 67% CCA 625 25 mm² (AWG 4) to 2.3 m, 7.5 ft 44.9 ft 150 mm² 4.8% to 5.0%
BOW5524D 24 V 205 A 125 A ZE125 61% CCA 342 25 mm² (AWG 4) to 8.4 m, 27.6 ft 164.7 ft 150 mm² 4.9%
BOW6012D 12 V 300 A 200 A ZE200 67% CCA 500 25 mm² (AWG 4) to 2.9 m, 9.5 ft 56.4 ft 150 mm² 5.0%
BOW6024D 24 V 165 A 100 A ZE100 61% CCA 275 25 mm² (AWG 4) to 10.3 m, 33.8 ft 204.4 ft 150 mm² 4.9%
BOW7512D 12 V 550 A 355 A ZE355 65% CCA 917 50 mm² (AWG 1) to 3.1 m, 10.2 ft 30.8 ft 150 mm² 5.0%
BOW7524D 24 V 315 A 200 A ZE200 63% CCA 525 25 mm² (AWG 4) to 5.4 m, 17.7 ft 107 ft 150 mm² 4.9%
BOW9512D 12 V 650 A 425 A ZE425 65% CCA 1083 50 mm² (AWG 1) to 2.6 m, 8.5 ft 25.9 ft 150 mm² 4.9%
BOW9524D 24 V 320 A 200 A ZE200 63% CCA 533 25 mm² (AWG 4) to 5.4 m, 17.7 ft 106.6 ft 150 mm² 5.0%
BOW12512D 12 V 840 A 500 A ZE500 60% CCA 1400 50 mm² (AWG 1) to 2 m, 6.6 ft 21 ft 150 mm² 4.8% to 5.1%
BOW12524D 24 V 470 A 300 A ZE300 64% CCA 783 50 mm² (AWG 1) to 7.3 m, 24 ft 71.9 ft 150 mm² 4.9%
BOWA0301 12 V 199 Aat 10.5 V, and 174 A at 12 250 A ZE250thruster fuse 200 A 144% 1 x 90 Ah - 12 V 35 mm² (AWG 2) to 6 m, 19.7 ft 84.6 ft 150 mm² 4.9%
BOWA0304feet column misprinted, see note 48 V 50 Aat 42 V, and 45 A at 48 100 A ZE100thruster fuse 80 A 222% 4 x 60 Ah - 12 V 25 mm² (AWG 4) to 48.2 m, 140.4 ft 672.6 ft 120 mm² 3.5%
BOWA0651 12 V 271 Aat 10.5 V, and 237 A at 12 300 A ZE300thruster fuse 250 A 127% 1 x 170 Ah - 12 V 50 mm² (AWG 1) to 6.3 m, 20.7 ft 62 ft 150 mm² 5.0%
BOWA0764 48 V 93 Aat 42 V, and 82 A at 48 125 A ZE125thruster fuse 100 A 152% 4 x 60 Ah - 12 V 25 mm² (AWG 4) to 37.7 m, 123.7 ft 598.8 ft 120 mm² 5.1%
BOWB150 24 V 276 Aat 21 V, and 242 A at 24 355 A ZE355thruster fuse 300 A 147% 2 x 170 Ah - 12 V 50 mm² (AWG 1) to 6.3 m, 20.7 ft 61.4 ft 150 mm² 2.5%
BOWB180 48 V 289 Aat 42 V, and 238 A at 44 300 A ZE300thruster fuse 250 A 126% 4 x 185 Ah - 12 V 50 mm² (AWG 1) to 6 m, 19.7 ft 59.1 ft 150 mm² 1.2% to 1.3%
BOWB210 48 V 300 Aat 42 V, and 275 A at 44 300 A ZE300thruster fuse 250 A 109% 4 x 185 Ah - 12 V 50 mm² (AWG 1) to 5.5 m, 18 ft 52.5 ft 150 mm² 1.2%
STE5512D 12 V 375 A 250 A ZE250 67% CCA 625 25 mm² (AWG 4) to 2.3 m, 7.5 ft 44.9 ft 150 mm² 4.8% to 5.0%
STE6012D 12 V 300 A 200 A ZE200 67% CCA 500 25 mm² (AWG 4) to 2.9 m, 9.5 ft 56.4 ft 150 mm² 5.0%
STE7512D 12 V 550 A 355 A ZE355 65% CCA 917 50 mm² (AWG 1) to 3.1 m, 10.2 ft 30.8 ft 150 mm² 5.0%
STE9512D 12 V 650 A 425 A ZE425 65% CCA 1083 50 mm² (AWG 1) to 2.6 m, 8.5 ft 25.9 ft 150 mm² 4.9%
BOW16024D 24 V 560 A 355 A ZE355 63% CCA 933 50 mm² (AWG 1) to 6.2 m, 20.3 ft 60.4 ft 150 mm² 5.0%
BOW22024D 24 V 760 A 500 A ZE500 66% CCA 1267 50 mm² (AWG 1) to 4.5 m, 14.8 ft 44.3 ft 150 mm² 5.0%
BOW28548D 48 V 560 A 355 A ZE355 63% CCA 933 50 mm² (AWG 1) to 6.2 m, 20.3 ft 60.4 ft 150 mm² 2.5%
BOWA0361 12 V 273 Aat 10.5 V, and 240 A at 12 355 A ZE355thruster fuse 300 A 148% 1 x 170 Ah - 12 V 50 mm² (AWG 1/0) to 6.3 m, 20.7 ft 61.7 ft 150 mm² 4.9%
BOWA0364 48 V 71 Aat 42 V, and 61 A at 48 125 A ZE125thruster fuse 100 A 205% 4 x 60 Ah - 12 V 25 mm² (AWG 4) to 42 m, 137.8 ft 692.3 ft 120 mm² 4.3% to 4.6%
BOWA0421 12 V 250 Aat 10.5 V, and 218 A at 12 355 A ZE355thruster fuse 300 A 163% 1 x 145 Ah - 12 V 35 mm² (AWG 2) to 4.8 m, 15.7 ft 67.3 ft 150 mm² 5.0%
BOWA0571 12 V 337 Aat 10.5 V, and 295 A at 12 355 A ZE355thruster fuse 300 A 120% 1 x 185 Ah - 12 V 50 mm² (AWG 1) to 5 m, 16.4 ft 49.9 ft 150 mm² 4.8% to 4.9%
BOWB057 24 V 189 Aat 21 V, and 141 A at 24 250 A ZE250thruster fuse 200 A 177% 2 x 90 Ah - 12 V 35 mm² (AWG 2) to 7 m, 23 ft 88.6 ft 150 mm² 2.4% to 2.7%
BOWB065 24 V 137 Aat 10.5 V, and 119 A at 12 200 A ZE200thruster fuse 160 A 168% 2 x 90 Ah - 12 V 35 mm² (AWG 2) to 17.5 m, 57.4 ft 246.1 ft 150 mm² 4.9%
BOWB076 24 V 184 Aat 21 V, and 166 A at 24 250 A ZE250thruster fuse 200 A 151% 2 x 90 Ah - 12 V 35 mm² (AWG 2) to 7 m, 23 ft 88.6 ft 150 mm² 2.3% to 2.6%
BOWB090 24 V 220 Aat 21 V, and 192 A at 24 250 A ZE250thruster fuse 200 A 130% 2 x 145 Ah - 12 V 50 mm² (AWG 1) to 8 m, 26.2 ft 78.7 ft 150 mm² 2.4% to 2.6%
BOWB110 24 V 330 Aat 21 V, and 288 A at 24 355 A ZE355thruster fuse 300 A 123% 2 x 170 Ah - 12 V 50 mm² (AWG 1) to 5 m, 16.4 ft 49.9 ft 150 mm² 2.4%
BOWB130 24 V 345 Aat 21 V, and 300 A at 24 355 A ZE355thruster fuse 300 A 118% 2 x 185 Ah - 12 V 50 mm² (AWG 1) to 4.9 m, 16.1 ft 64.6 ft 150 mm² 2.4% to 3.3%
BOWB285 48 V 415 Aat 42 V, and 365 A at 48 425 A ZE425no thruster fuse 116% 4 x 220 Ah - 12 V 50 mm² (AWG 1) to 4 m, 13.1 ft 42.6 ft 150 mm² 1.2% to 1.3%
BOWB300 48 V 432 Aat 42 V, and 378 A at 48 425 A ZE425no thruster fuse 112% 4 x 220 Ah - 12 V 50 mm² (AWG 1) to 3.5 m, 11.5 ft 41 ft 150 mm² 1.1% to 1.3%
BOWB320 48 V 445 Aat 42 V, and 390 A at 48 425 A ZE425no thruster fuse 109% 4 x 220 Ah - 12 V 70 mm² (AWG 2/0) to 4.5 m, 14.8 ft 39.4 ft 150 mm² 1.0% to 1.3%
BOWB385 48 V 540 Aat 42 V, and 480 A at 48 500 A ZE500no thruster fuse 104% 4 x 220 Ah - 12 V 2 × 70 mm² (AWG 2/0) to 2 m, 6.6 ft 6.6 ft 150 mm² 0.3% to 0.6%
BOWB420 48 V 595 Aat 42 V, and 520 A at 48 500 A ZE500no thruster fuse 96% 4 x 220 Ah - 12 V 2 × 70 mm² (AWG 2/0) to 2 m, 6.6 ft 6.6 ft 150 mm² 0.3% to 0.7%

The AWG column needs the same reading as Sleipner's, and it points the other way. Where Sleipner's AWG size is the larger conductor, VETUS's is the smaller. On every size but 150 mm², it names the AWG size below the metric figure by area.

Two manuals are the exception. In the 110 mm and 125 mm BOW PRO manuals the aught sizes (1/0 to 4/0) are written "AWG 0, 00, 000, 0000". Those two give 50 mm² as AWG 0, the nearest size. Every other VETUS manual gives AWG 1.

Show VETUS's AWG column against its metric sizes (8 rows)
Every metric size VETUS prints, beside the AWG size it prints for it. The last column is how much copper that AWG size has as a share of the metric one, computed from the AWG definition. These 8 pairings cover 388 bands across 42 rows.
Their mm² Their AWG Copper, AWG size as % of metric Direction
25 4 84.6% less copper than the metric size
35 2 96.1% less copper than the metric size
50 1 84.8% less copper than the metric size
50 1/0110 and 125 mm manuals only 106.9% more copper than the metric size
70 2/0 96.3% less copper than the metric size
95 3/0 89.5% less copper than the metric size
120 4/0 89.3% less copper than the metric size
150 300 MCM 101.3% more copper than the metric size

Buy to VETUS's AWG column and at 25 mm² you have 15% less copper than the metric column asks for. The band tops then compute to as much as 6.0%. That is still inside the manual's 10 percent, because the table started at half of it.

If you want the cable the table was built to, buy the metric size, or go one AWG size up from the one printed.

The table has changed over the years. The December 2019 revision of the BOW55 manual gave each voltage one band. At 12 V it was 70 mm² (printed "AWG 00") to 12 m, 40 ft, which computes to 9.2% at the stated 375 A. At 24 V it was 35 mm² to 23 m, 9.7%. That table was built to the ten percent the text states.

The May 2026 revision prints 11 bands per voltage at the same 375 A, and the same 70 mm² now reaches only 6.4 m. The older table also printed the 24 V fuse as 125 A beside the part number ZE250, which is the 250 A fuse. The new one prints ZE125.

If your manual came in the box a few years ago, check the current one on vetus.com before you buy cable.

Two more things in the manuals. The BOW PRO tables name two fuses: a main fuse at the battery and a smaller "thruster fuse" inside the motor controller. The manual says this of the thruster fuse: "This fuse protects the controller and motor against short circuit/overloading and it must remain present under all circumstances".

The main fuse figure comes with a condition: "The recommended value of the main fuse applies exclusively to a power supply system in which the bow thruster is the only power consumer." The 110 mm manual also has an odd row. Its BOWA0304 row's feet column is not its meter column converted. There 48.2 m is printed as 140.4 ft, and every band in that row is off by the same share. The drop for that row is computed from the meters.

The larger manuals, read 15 September 2026, add these:

  • The 48 V BOW28548D manual prints the 24 V BOW16024D's table line for line: the same 560 A, battery, fuse and bands. At twice the voltage the same cable loses half the share, so its bands compute to 2.5%.
  • In the 185 mm Boosted manual the BOWB065 is built to five percent like the brushed range, 4.9%. Its four siblings on the same page sit at 2.3% to 3.3%. The same manual's BOWB130 row prints one band backwards, in both the meter and the feet columns. It reads 13.7 to 19.7 m for 150 mm², then 19.7 to 18.6 m for 2 × 95 mm².
  • The 300 and 400 mm Boosted manuals print one fuse, not two, and it sits closer to the draw than the smaller units'. It runs 96% to 116% of the nominal figure, and on the BOWB420 it drops below: 500 A on a 520 A draw. On every smaller BOW PRO the main fuse sits above the draw with a thruster fuse in the controller under it.
  • The 125 mm BOW PRO manual prints a larger current for the smaller unit, at both voltages. The BOWA0361 (36 kgf) draws 240 A against the BOWA0421 (42 kgf) at 218 A.
  • A Boosted unit's bank is charged from the boat's 12 or 24 V system, and the 185, 300 and 400 mm manuals print a second table for that feed cable. These are looser than the thruster tables: at the charger's printed current the 24 V feed rows compute to 7.4% to 11.1% at their worst band top. The 250 mm manual prints no feed table.
  • The 185 mm manual prints one feed table under both a 12 V and a 24 V heading. At the charger's 80 A the 12 V row computes to 18.4%, well over the manual's own 10 percent. That table's feet column is also not its meter column converted (40 m printed as 35.1 ft).
  • The RIMDRIVE manual (2017) prints no band table. It gives a cable range per model (RD125: 35 to 50 mm²; RD160: 50 to 70 mm²). It names a 200 A main fuse (ZE200) and a 425 A fuse in the connection unit. It has one rule for the larger size: "Use the largest cable diameter for cable lengths of more than 10 m ( 33 ft) and/or for an expected continuous use of more than 5 minutes."
  • The BOW PRO user manual (June 2026) prints one fuse per model. It matches the installation manuals above on every one of the 22 models they share. Where an installation manual gives two fuses, it matches the controller fuse. Where it gives one, it matches the main fuse. The October 2024 revision printed four of them differently: BOWA0304 125 A, now 80; BOWA0651 300 A, now 250; BOWB210 300 A, now 250; BOWB285 355 A, now 425.

The VETUS review reads the rest of these manuals. The battery page has the minimum and maximum battery for each model and what changed between revisions.

What Lewmar publishes: one cable and one run per model, built to about a volt

Lewmar's Gen 2 installation manual has a table headed "Correct cable sizes". It gives each model and voltage three figures: a stated current draw, the smallest cable in mm², and the longest run that size will carry. There is no American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still. column.

The table carries a note about the run: "Cable length is total from battery to thruster and back."

We computed each row at the stated current, on that cable, over that run. Every one of the 15 rows loses between 0.83 V and 0.96 V. That is a fixed number of volts, whatever the system voltage:

  • 6.9% to 7.8% on the seven 12 V rows
  • 3.7% to 4.0% on the six 24 V rows
  • 1.8% to 1.9% on the two 48 V rows

So a 12 V Lewmar at its longest allowed run sits inside ABYC's 10 percent and outside its 3 percent. A 24 V one lands within a point above the 3 percent figure. A 48 V one is under it.

The manual's own floor is looser than its table. It says: "The minimum voltage at motor when running should be 10V for 12V and 21V for 24 V units". That allows 2 and 3 volts of loss.

Show Lewmar's Gen 2 cable table (15 rows)
Lewmar, one row per model and voltage, from section 4.5 of the Gen 2 installation manual (559231 Iss.3) and the fuse column of its ladder, read 15 September 2026. The drop is computed at the stated current on the maker's cable over the maker's longest run. The US size is the smallest AWG size with at least the metric copper, so it is never smaller than Lewmar asks for. Where the metric size holds more copper than one 4/0, it is the smallest pair of one size per leg that holds it, up to two 4/0. Past two 4/0 per leg no common marine cable matches, and the cell says so. The last column is the draw as a share of ABYC's continuous ampacity for the US size, clear of the engine compartment, a pair counted together.
Model Volts Draw Fuse Their cable Their longest run Drop at that run US size Draw as % of ampacity
110 1.5KW 12 V 215 A 200 A 93% of draw 50 mm² 12 m 39.4 ft 7.4% 0.89 V 1/0 75%
140 2.0KW 12 V 270 A 200 A 74% of draw 70 mm² 14 m 45.9 ft 7.8% 0.93 V 3/0 70%
140 2.2 KW 12 V 280 A 200 A 71% of draw 70 mm² 12 m 39.4 ft 6.9% 0.83 V 3/0 73%
185 3 KW 12 V 330 A 250 A 76% of draw 95 mm² 15 m 49.2 ft 7.5% 0.90 V 4/0 74%
185 3 KW 24 V 160 A 130 A 81% of draw 35 mm² 12 m 39.4 ft 3.9% 0.95 V 1 65%
185 4 KW 12 V 470 A 400 A 85% of draw 150 mm² 16 m 52.5 ft 7.2% 0.86 V 2 x 3/0 61%
185 4 KW 24 V 235 A 130 A 55% of draw 70 mm² 16 m 52.5 ft 3.9% 0.93 V 3/0 61%
185 5 KW 12 V 480 A 400 A 83% of draw 185 mm² 21 m 68.9 ft 7.8% 0.94 V 2 x 4/0 54%
185 5 KW 24 V 240 A 130 A 54% of draw 70 mm² 15 m 49.2 ft 3.7% 0.89 V 3/0 62%
185 6 KW 12 V 700 A 500 A 71% of draw 300 mm² 22 m 72.2 ft 7.4% 0.89 V Over 2 x 4/0 no common size
185 6 KW 24 V 370 A 325 A 88% of draw 120 mm² 18 m 59.1 ft 4.0% 0.96 V 2 x 2/0 56%
250 8 KW 24 Vprinted "224" 500 A 400 A 80% of draw 185 mm² 20 m 65.6 ft 3.9% 0.93 V 2 x 4/0 56%
250 9.6 KW 48 V 330 A 250 A 76% of draw 95 mm² 15 m 49.2 ft 1.9% 0.90 V 4/0 74%
300 10.8 KW 24 V 650 A 400 A or 500 A 62% to 77% of draw 300 mm² 25 m 82.0 ft 3.9% 0.93 V Over 2 x 4/0 no common size
300 15.0 KW 48 V 420 A 400 A 95% of draw 150 mm² 18 m 59.1 ft 1.8% 0.87 V 2 x 3/0 55%

Read the US size column with care on the big units. Of the 15 rows, seven name a metric size with more copper than a single 4/0:

  • On five of them, a pair of one size per leg holds it.
  • On the other two, the metric size holds more copper than two 4/0 per leg, past any common marine cable. A shorter run is the common-cable answer there.

Industrial cable above 4/0 exists, but it is not common marine stock, and ABYC's table stops at 4/0.

The fuse column runs the way VETUS's brushed units do above. The ladder prints a fuse for every electric model, and every one is below the stated draw, 54% to 95% of it.

Three 24 V 185 mm units share one 130 A fuse: the 3, 4 and 5 kW, drawing 160 A, 235 A and 240 A. On the 5 kW that fuse is 54% of the draw.

The 300 10.8 kW at 24 V has two fuses on the ladder for one current figure: 400 A on the aluminum-gearbox part number and 500 A on the bronze.

Lewmar's whole battery rule is one sentence: "Battery crank capacity should be at least equal to the thruster current."

The battery page puts it beside the other makers'.

Under the table sits a worked example: "a total of 28 m (92 ft) of cable with a model 250 8.0 kW thruster would need 95 mm CSA (000 AWG) cable".

The row above it says 185 mm² to 20 m. At the row's 500 A, the example's cable over the example's run loses 2.54 V. That is 10.6% of 24 V, over ABYC's 10 percent and 2.7 times the row's own figure.

The example belongs to the previous manual. Issue 2 covered the 140TT, 185TT and 250TT. It printed a table of the longest run for each of eight cable sizes, and its 250TT 8.0 kW cell on 95 mm² reads 28 m.

The Gen 2 manual replaced the table and kept the example. Its "000" is the AWG size nearest 95 mm² by area, 3/0. It is the one place the section gives an AWG size at all.

Show the pre-Gen 2 Lewmar table (9 rows)
The pre-Gen 2 table, from page 15 of the Issue 2 manual (140TT, 185TT and 250TT), read 15 September 2026. For each model it gives the longest total run "from battery to thruster and back" on each of eight cable sizes. The meters are printed by metric size (25, 35, 50, 70, 95, 120, 150, 175 mm²). The feet are printed by AWG size (3, 2, 1, 1/0, 2/0, 3/0, 4/0, 2 x 4/0). The loss columns are computed at the stated current across every recommended cell of each table.
Model Volts Draw Smallest size, its run Largest size, its run Loss, meter cells Loss, feet cells As % of voltage
140TT 2.2kW 12 V 280 A 25 mm², 6 m 70 mm², 21 m 1.16 to 1.45 V 1.10 to 1.39 V 9.2% to 12.1%
185TT 3.0kW 12 V 330 A 25 mm², 6 m 95 mm², 21 m 1.14 to 1.37 V 1.20 to 1.26 V 9.5% to 11.4%
185TT 3.0kW 24 V 160 A 25 mm², 18 m 35 mm², 22 m 1.73 to 1.99 V 1.99 to 2.00 V 7.2% to 8.3%
185TT 4.5kW 12 V 480 A 25 mm², 4 m 175 mm², 29 m 1.32 to 1.42 V 1.11 to 1.39 V 9.2% to 11.8%
185TT 4.5kW 24 V 240 A 25 mm², 12 m 70 mm², 32 m 1.89 to 1.99 V 1.87 to 2.02 V 7.8% to 8.4%
185TT 6.0kW 12 V 700 A 50 mm², 6 m 175 mm², 28 m 1.38 to 1.93 V 1.38 to 1.72 V 11.5% to 16.1%
185TT 6.0kW 24 V 370 A 25 mm², 9 m 95 mm², 32 m 2.04 to 2.30 V 2.06 to 2.22 V 8.5% to 9.6%
250TT 8.0kW 24 V 500 A 25 mm², 7 m 150 mm², 45 m 2.07 to 2.59 V 2.50 to 2.60 V 8.6% to 10.8%
300TT 10.0kW 24 V 650 A 25 mm², 4 m 175 mm², 30 m 1.79 to 2.02 V 1.92 to 2.07 V 7.5% to 8.6%

The old table was built to a share of the voltage, and a bigger one:

  • the four 12 V rows lose 1.10 V to 1.93 V, 9.2% to 16.1%
  • the five 24 V rows lose 1.73 V to 2.60 V, 7.2% to 10.8%

Both straddle ABYC's 10 percent. Every cell of the old table allows more loss than any row of the Gen 2 table.

Its feet table is not the meter table converted. Of the 49 cells that appear in both, 43 are more than a foot away from a conversion, because each table was worked on its own sizes.

For example, the 140TT 2.2kW's 35 mm² cell is 10 m, 32.8 ft, and its AWG 2 cell is 30 ft. If you own a pre-Gen 2 unit and size from its own manual, you are sizing to that older, looser table.

The Lewmar review reads the rest of both manuals: the warranty's one-year exceptions, the run-time rule, and the boat-length bands the maker does not publish.

What Quick publishes: cable by run length and a fuse, and no current

Quick's BTQ installation manual gives every model two things. The first is a fuse, as a CNL DIN rating (a bolt-down fuse standard). The second is a cable cross-section in three bands of total run.

The cable table is footnoted "L = positive cable + negative cable".

The bands are under 5 m, 5.1 to 10 m, and 10.1 to 20 m. Each gives a metric size with an American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still. size in brackets, and "2 x" where a leg needs two conductors.

Neither of its manuals gives a current draw. Without one, no drop can be computed. The warning in the draw section about working amps from kilowatts applies here as much as anywhere. The table prints what Quick prints and computes only what the table itself can say.

Show Quick's table, one row per BTQ model (24 rows)
Quick, one row per BTQ model, from the technical data pages of the BTQ series manual (REV003A), read 15 September 2026. The three cable columns are the maker's. The last column is the meters of run per mm² of copper at the top of the long band, divided by the same at the top of the short band. It shows how much more loss the table accepts at 20 m than at 5 m, whatever the current turns out to be.
Model Volts Motor Fuse Under 5 m 5.1 to 10 m 10.1 to 20 m Long band over short
BTQ 1102512 12 V 1.3 kW 130 A 35 mm² (AWG 2) 50 mm² (AWG 1) 70 mm² (AWG 2/0) 2.0 times
BTQ 1253012 12 V 1.5 kW 225 A 50 mm² (AWG 1) 70 mm² (AWG 2/0) 95 mm² (AWG 3/0) 2.1 times
BTQ 1254012 12 V 2.2 kW 325 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 1403012 12 V 1.5 kW 150 A 35 mm² (AWG 2) 50 mm² (AWG 1) 70 mm² (AWG 2/0) 2.0 times
BTQ 1404012 12 V 2.2 kW 225 A 50 mm² (AWG 1) 70 mm² (AWG 2/0) 95 mm² (AWG 3/0) 2.1 times
BTQ 1805512 12 V 3 kW 250 A 50 mm² (AWG 1) 70 mm² (AWG 2/0) 95 mm² (AWG 3/0) 2.1 times
BTQ 1805524 24 V 3 kW 150 A 35 mm² (AWG 2) 50 mm² (AWG 1) 70 mm² (AWG 2/0) 2.0 times
BTQ 1807512 12 V 4 kW 350 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 1807524 24 V 4 kW 250 A 50 mm² (AWG 1) 70 mm² (AWG 2/0) 95 mm² (AWG 3/0) 2.1 times
BTQ 1809512 12 V 6 kW 350 A 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2 × 95 mm² (AWG 3/0) 2.1 times
BTQ 1809524 24 V 6 kW 250 A 50 mm² (AWG 1) 70 mm² (AWG 2/0) 95 mm² (AWG 3/0) 2.1 times
BTQ 1806512 12 V 3.3 kW 275 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 1806524 24 V 3.3 kW 175 A 50 mm² (AWG 1) 70 mm² (AWG 2/0) 95 mm² (AWG 3/0) 2.1 times
BTQ 1808512 12 V 4.3 kW 400 A 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2 × 95 mm² (AWG 3/0) 2.1 times
BTQ 1808524 24 V 4.3 kW 275 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 1810512 12 V 6.3 kW 400 A 2 × 70 mm² (AWG 2/0) 2 × 95 mm² (AWG 3/0) 2 × 120 mm² (AWG 4/0) 2.3 times
BTQ 1810524 24 V 6.3 kW 275 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 2512012 12 V 6.5 kW 500 A 2 × 70 mm² (AWG 2/0) 2 × 95 mm² (AWG 3/0) 2 × 120 mm² (AWG 4/0) 2.3 times
BTQ 2512024 24 V 6.5 kW 275 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 2514024 24 V 8 kW 275 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2.0 times
BTQ 2524024 24 V 10 kW 500 A 2 × 50 mm² (AWG 1) 2 × 70 mm² (AWG 2/0) 2 × 95 mm² (AWG 3/0) 2.1 times
BTQ 3025024 24 V 10 kW 400 A 70 mm² (AWG 2/0) 2 × 50 mm² (AWG 1) 2 × 95 mm² (AWG 3/0) 1.5 times
BTQ 3027024 24 V 12 kW 500 A 95 mm² (AWG 3/0) 2 × 95 mm² (AWG 3/0) 2 × 120 mm² (AWG 4/0) 1.6 times
BTQ 3030048 48 V 15 kW 500 A 95 mm² (AWG 3/0) 2 × 70 mm² (AWG 2/0)bracket printed without the "2 x" 2 × 95 mm² (AWG 3/0) 2.0 times

The last column is the table's own shape. At one current, the loss over a run is the run divided by the copper. So meters per mm² at the top of a band measures the loss that band accepts, up to the current the maker leaves out.

On the long band it is 1.5 to 2.3 times what it is on the short band. Quick accepts between one and a half and two and a third times the loss at 20 m that it accepts at 5 m. A short run on Quick's minimum cable carries the margin, and a long one does not.

VETUS's tables above work the other way. On 40 of its 42 rows, the bands spread by no more than 1.3 times. The two that spread more, the BOWB385 and BOWB420, are the rows whose table offers two sizes for one run.

Quick's AWG column rounds down like VETUS's. It uses five pairings: 35 mm² as AWG 2, 50 mm² as AWG 1, 70 mm² as AWG 2/0, 95 mm² as AWG 3/0, 120 mm² as AWG 4/0. All of them name the AWG size below the metric one by area. They run from 85% of the metric copper on 50 mm² to 96% on 70 mm².

One cell, the BTQ 3030048's middle band, prints "2 x 70 mm2" beside a bracket of "AWG 2/0" with no "2 x".

The BTQ250 and BTQ300 manual (REV006C) prints one "Section of wire" per model and no run length. Set that against the three-band table's 10.1 to 20 m band for the same model.

It is the same on three models (BTQ 2524024, BTQ 3025024, BTQ 3030048). It is smaller on four (BTQ 2512012, 2 × 95 mm² against 2 × 120 mm²; BTQ 2512024, 120 mm² against 2 × 70 mm²; BTQ 2514024, 120 mm² against 2 × 70 mm²; BTQ 3027024, 2 × 95 mm² against 2 × 120 mm²). On the BTQ 2512012 and BTQ 3027024 it is the three-band table's middle band.

The REV006C fuse column agrees with REV003A on six of the seven models. The BTQ 2524024's fuse cell prints "(2 x AWG 3/0)" where REV003A prints 500 A.

The fuse is the one current-shaped figure Quick prints, and it is not a draw. Two makers above print both. On each of them, every brushed unit's fuse sits below its stated draw: VETUS's at 60% to 73% of it, Lewmar's at 54% to 95%.

Read Quick's 130 A on the BTQ 1102512 as the fuse it is. Get the draw from the installer or the maker before sizing anything from it.

The Quick review reads the rest of both manuals, the run-time rule that lives in the control panel's manual, and the three sets of boat-length bands.

What Max Power publishes: a cable table at two currents, and a fuse sized to the cable

Max Power's CT100/CT125 manual gives each of its two units two current figures, two pages apart. The first is on the performance page, where the data "is measured with an approx. consumption of 680A and 11V for the CT100, or 430A and 22V for the CT125".

The second is in the fuse table, which gives the same units a "Maximum Amperage" of 550 A and 330 A. The cable table is four bands of total run, both legs counted, in mm² with no American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still. column.

We computed the drop at both currents:

  • At the maximum amperage, the CT100's bands hold 4.2% to 5.3% of 12 V, and the CT125's 2.4% to 4.0% of 24 V.
  • At the measured consumption, they hold 5.1% to 6.5% and 3.1% to 5.1%.

Every band is inside ABYC's 10 percent at both currents. Only one of the eight, the CT125's shortest, is under the 3 percent figure at the maximum amperage.

Show Max Power's cable table (8 bands)
Max Power, one row per band, from sections 7 to 9 of the CT100/CT125 manual (last update July 2024), read 15 September 2026. The drop is computed on the maker's cable at the top of each band, once at the fuse table's maximum amperage and once at the measured consumption. The US size follows the Lewmar table above. It is the smallest AWG size with at least the metric copper, or a pair of one size per leg above one 4/0. Past two per leg it reads "Over 2 x 4/0", where no common marine cable matches. The last column is the maximum amperage as a share of ABYC's continuous ampacity for that size, clear of the engine compartment, a pair counted together.
Model Volts Run to Their cable Drop at maximum amperage Drop at measured consumption US size Maximum as % of ampacity
CT100 12 V 5 m 16.4 ft 95 mm² 4.2% 5.1% 4/0 124%
CT100 12 V 10 m 32.8 ft 150 mm² 5.3% 6.5% 2 x 3/0 71%
CT100 12 V 15 m 49.2 ft 240 mm² 4.9% 6.1% Over 2 x 4/0 no common size
CT100 12 V 20 m 65.6 ft 300 mm² 5.3% 6.5% Over 2 x 4/0 no common size
CT125 24 V 5 m 16.4 ft 50 mm² 2.4% 3.1% 1/0 116%
CT125 24 V 10 m 32.8 ft 70 mm² 3.4% 4.4% 3/0 86%
CT125 24 V 15 m 49.2 ft 95 mm² 3.7% 4.9% 4/0 74%
CT125 24 V 20 m 65.6 ft 120 mm² 4.0% 5.1% 2 x 2/0 50%

The manual says how the fuse is sized: "on the basis of the cable sections in the circuit and NOT the amperage drawn by the appliance".

CT100: a 315 A ceramic or 400 A ANL fuse. That is 57% and 73% of its maximum amperage, and 46% and 59% of its measured consumption.

CT125: a 200 or 225 A fuse, 61% and 68% of its maximum.

Both fuses sit below both currents on both units. That is the same direction as every VETUS brushed unit and every Lewmar row above.

Of the eight bands, four name more copper than a single 4/0. A US owner running a CT100 more than 5 m there and back is into a pair of one size per leg.

Past 10 m, the manual's size holds more copper than two 4/0 per leg, past any common marine cable. A shorter run is the common-cable answer there.

The Max Power review reads the rest of the manual. It covers the battery the manual asks for, the one an owner was told to fit, the run-time rule and the selection chart.

What each maker publishes, and what none does

Six makers put figures on this page. Sleipner, VETUS, Lewmar and Max Power published a current and a cable table each, Max Power with two currents. Quick published a cable table and a fuse with no current. Sideshift published a start current, a cable size and a distance.

Here is what this page holds for each brand:

Sleipner. A stated current draw, a minimum battery in Cold cranking amps: how much current a battery can deliver in a short, hard burst, which is the rating starter batteries carry. A thruster draws like a starter, so the makers size its battery this way rather than by capacity. and a full cable table in both metric and American wire gauge, the size scale for electrical cable. The number falls as the cable gets thicker: 2 AWG is thicker than 6, and 1/0, 2/0, 3/0 and 4/0 are thicker still., in the installation manual, free to download. The current guides print an ANL fuse per model, and Sleipner's webshop sells the fuses and names the models each one fits.

VETUS. Every installation manual is free to download. Each gives a stated current, a minimum and maximum battery, a full cable table in mm² and AWG, and a numeric fuse with its part number. The section above holds 42 rows from 21 manuals.

Lewmar. A stated current, a smallest cable and a longest run per model in the Gen 2 installation manual, and a fuse per model on its ladder. No AWG column, and a worked example carried over from the previous manual's table. The section above holds 15 rows from the Gen 2 table and 9 from the older one.

Quick. A fuse and a cable size for three bands of total run per model, in mm² and AWG, in the BTQ installation manual. No current draw in either manual. The section above holds 24 rows.

Sideshift. A start current per series, one cable size per series, and a battery distance printed two ways, above. No running current and no cable table by length.

Max Power. Two current figures, a four-band cable table in mm² and two fuse ratings for each of the CT100 and CT125, in one installation manual. No AWG column. Its other tunnel manuals and its stern pod manual print a cable table each in the same four bands, 37 columns across 24 manuals, and the wiring calculator reads them. The section above holds the CT100/CT125 manual's 8 bands.

Where to go next

More in this section: DIY thruster installation Stern thruster installation Sailboat bow thruster installation Bow and stern thruster battery calculator Bow thruster tunnel placement Aluminum and steel boat bow thrusters

The cable sizes, fuses and voltage drops on this page are estimates for planning. They are not an inspection of your boat. Check any cable, fuse or battery against the maker's manual and with your yard before you buy or install anything. The full wording is in our terms.